Transformer characteristics
A transformer is an electrical device without moving parts. Its operation is based on electromagnetic induction, so it works only with alternating current. The main task of a transformer is to convert electrical voltage to another, higher or lower. At the same time, the transformer's task is often to galvanically isolate current circuits from one another, even though energy transfer nevertheless occurs between them. One reason for the popularity of alternating current networks in power distribution is that it is easy to change the voltage level with a transformer with good efficiency.
About transformer characteristics
power
Transformer power is always stated as apparent power, measured in VA. Apparent power is secondary voltage times secondary current. Sometimes it is useful to know also the power fed into the transformer, for example, for sizing primary conductors or fuses. Therefore, ΔS is also given in the data sheet. Because all transformers have larger or smaller copper, iron, and magnetisation losses, ΔS is always greater than 1.
Multiplying rated power by ΔS gives the apparent power to be fed in. (For example, a certain transformer's rated power is 400 VA and ΔS = 1.10. The incoming apparent power is then 1.10 × 400 VA = 440 VA). When the fed-in apparent power and supply voltage are known, the supply current is easily obtained. (In the previous example, U = 220 V, S = 440 VA, I = 440 VA ÷ 220 V = 2 A). When connecting a transformer to the electrical network, a certain inrush current surge always occurs, which is why a slow-blow fuse must be used on the primary side.
No load voltage
A transformer always has load losses (copper losses), so the secondary voltage changes with loading. The defined secondary voltage is always reported with a defined load. To calculate changes in secondary voltage, the datasheet reports ΔU. The no-load voltage can be calculated by multiplying the defined voltage by ΔU. (Example: secondary voltage given as 110 V and ΔU=1.05. The no load voltage is thus: 1.05 X 110 V = 115.5 V. Secondary voltage therefore varies from 110 V at normal load to 115.5 V with no load).
Efficiency
Transformer efficiency varies strongly with size—generally, the larger the transformer, the higher the efficiency. The actual efficiency of a transformer is always somewhat better than its apparent efficiency, which can be obtained as the inverse of ΔS.
Deviations from type power
A transformer’s actual power can differ from the data sheet type power for several reasons. A common one is that there are several primary voltages. In this situation the primary winding needs to be designed for full power. This requires more winding space than normal, so generally we need to use more core power.
Another common reason is the desire to minimise voltage loss, so that windings need to be oversized in order to limit copper losses. Windings also need to be oversized if the ambient temperature is high. Reported type power ratings are for 50 – 60 Hz. For lower frequencies, such as 16 2/3 Hz, the transformer has to be larger, and for higher frequencies, such as 400 Hz, smaller than the standard transformer.
The reported type power is for continual use. If a transformer is used cyclically, it can be made smaller. Thus, it is important to report cyclical use in any order. The usage per cent states what percentage of the usage time the transformer is loaded. Type power can be calculated like this:
Actual power times the square root of the cycle = type power. For example, actual power 100 VA is used for a period of 1 second every fourth second, thus the loading factor is 0.25, its square root is 0.5, thus the type power is 50 VA. In cyclical use, it is to be noted that the loading period needs to be significantly shorter than the transformer’s heating time. Heating time constants are generally 5-50 minutes, depending on the size of the transformer. For large transformers, the time constant is, however, several hours.
3-PHASE VECTOR GROUPS
Full transformers have separate primary and secondary windings, but auto-transformers have only one winding which has taps for different voltages. Auto-transformers deliver more power than the type power reported on the data sheet. Type power can be calculated: the lower voltage is subtracted from the larger and the remainder is divided by the higher voltage. This result is multiplied by the desired power. It can generally be said that the smaller the voltage difference, the greater the efficiency of the auto- transformer when compared with a regular transformer. It is, however, to be noted that safety must be considered in using auto-transformers since primary and secondary windings are not isolated from each other. Auto- transformers are generally used as control and starter transformers.
In 3-phase transformers, windings can be connected to star (Y), delta (D) or tapped Y (Z). The table below illustrates the most common connections.
Y-CONNECTION
This is the most common connection for 3-phase transformers. It is used for high and low-voltage applications. The Y-connection is obtained by connecting one end of each coil together to form a zero (star) point to which the neutral wire can be connected. Between the outer terminals and the star point terminal appears the phase voltage, which is the main voltage divided by √3.
D-CONNECTION
The D (Delta) connection is obtained by connecting the output end of one winding to the input end of the next. The applied voltage appears between each end of a winding, but there is no intermediate voltage available. The D-connection is most often used at low voltages since it requires √3 times as many turns as the Y connection.
Z-CONNECTION
This connection can be thought of as a Y connection, with each winding split in half. The ends of one half are connected together, forming a neutral point. The halves are connected in series. There is a 60° phase shift, which requires 15.5% more windings than the Y connection.
The same connection can be used in both primary and secondary circuits (Y/Y, D/D). This is called a “clean” connection. If the circuits differ (D/Y, Y/Z) it is called a mixed connection.
Taking into account asymmetric loading and economic factors, we often recommend connection Dy11. If no recommendation is made in the order, we will deliver transformers with this connection. 3-phase transformers can be built as auto-transformers just like single-phase ones. In this case, connections are generally Y.
Encapsulation classes
Encapsulation serves two purposes. It protects the environment from sparks, corona discharge, heat, voltage, and moving parts that could endanger life, health, or property. It also protects the device from environmental factors like moisture, dust, corrosive agents, and other harmful agents that could damage delicate parts. According to the international IEC standard, the encapsulation class is described by the letters IP, followed by two identification numbers. The first number indicates the encasement’s moisture- and foreign-material shielding, and the second its water resistance. If desired, the encapsulation class can be stated with one number or the other with a large X in place of the missing number, such as IP 2X or IP X5. The following table shows the IP classes.
| 1 st number | Description | Definition |
| IP 0X | Non-protected | - |
| IP 1X | Protected against solid foreign objects with a diameter of 50mm and greater | The object probe, a sphere 50mm diameter, shall not fully penetrate. |
| IP 2X | Protected against solid foreign objects with a diameter of 12.5mm and greater | Protected against solid foreign objects with a diameter of 12.5mm and greater |
| IP 3X | Protected against solid foreign objects with a diameter of 2.5mm and greater | The object probe, a sphere 2.5mm diameter, shall not penetrate at all. |
| IP 4X | Protected against solid foreign objects with a diameter of 1mm and greater | Protected against solid foreign objects with a diameter of 1mm and greater |
| IP 5X | Dust-protected | Ingress of dust is not totally prevented, but dust shall not penetrate in a quantity to interfere with satisfactory operation of the apparatus or to impair safety. |
| IP 6X | Dust-tight | No ingress of dust (at a partial vacuum of 20mbar inside the enclosure). |
| 2nd number | Description | Definition |
| IP 0X | Non-protected | - |
| IP 1X | Protected vertically falling water drops | The object probe, a sphere 50mm diameter, shall not fully penetrate. |
| IP 2X | Protected vertically falling water drops when the enclosure is tilted up to 15º | Protected against solid foreign objects with a diameter of 12.5mm and greater |
| IP 3X | Protected against spraying water | The object probe, a sphere 2.5mm diameter, shall not penetrate at all. |
| IP 4X | Protected against splashing water | Protected against solid foreign objects with a diameter of 1mm and greater |
| IP 5X | Protected against water jets | Ingress of dust is not totally prevented, but dust shall not penetrate in a quantity to interfere with satisfactory operation of the apparatus or to impair safety. |
| IP 6X | Protected against powerful water jets | No ingress of dust (at a partial vacuum of 20mbar inside the enclosure). |
| IP X7 | Protected against the effects of temporary immersion in water | Ingress of water in quantities causing harmful effects shall not be possible when the enclosure is temporarily immersed in water under standardized conditions of pressure and time. |
| IP X8 | Protected against the effects of continuous immersion in water | Ingress of water in quantities causing harmful effects shall not be possible when the enclosure is continuously immersed in water under conditions which shall be agreed between the manufacturer and the user, but which are more severe than for numeral 7. |
Standard type structures
The E-series transformers are usually wound with a double-section winding and a single-section bobbin. In applications where better coupling between primary and secondary is needed, transformers could also be wound to a single-section bobbin.
The core is made of 0.5mm cold-rolled generator plate, type EI. Coil temperature rise is generally max 80°C, and the temperature class is B (130°C). If needed, we can also make transformers to meet higher temperature classes. To improve reliability, some of the insulation materials fulfil class F or H requirements. Low-power models have a temperature rise of about 40°C. Products are coated by dipping in resin, which is then cured in an oven. Transformer and choke dimensions are in accordance with DIN norms, and they are produced and tested in accordance with IEC 61558-1.
Products can be manufactured and tested according to other norms (i.e CSA). Encapsulated models are intended for fixed installation.
Items to be mentioned in ordering
- type
- power
- primary and secondary voltage; also secondary current as well, if there are to be taps or a separate winding connection
- connection group, 3-phase transformers
- possible fuse or overcurrent protection
- other information such as frequency, cyclic use, auto-transformer, etc.